PlumbRevise
F-Gas Category 1

Refrigerant Families and Safety Classification

Note 2 of 5 · free to read

The main refrigerant families, how their GWP compares, and how the A/B and 1 to 3 safety classes work.

HFCs and their GWP

HFC refrigerants remain in existing equipment, but their climate effects vary. The values used for GB CO2e calculations include:

  • R404A: 3922.
  • R410A: 2088.
  • R134a: 1430.
  • R32: 675.

R32 is a single HFC with a lower GWP than R410A. It is still subject to the relevant F-gas duties and has a different flammability class; a lower figure is not permission to substitute it in equipment designed for another gas.

HFOs and natural refrigerants

HFOs such as R1234yf have very low GWP and may be used alone or in blends. Many are mildly flammable. They are not automatic drop-in replacements: equipment approval, pressure, lubricant and safety class must be checked. Pure HFOs listed in Annex II and blends containing Annex I HFCs do not have identical duties under the GB F-gas regime.

Natural refrigerants are outside the HFC family. R290 is propane, with very low GWP; R744 is carbon dioxide, the GWP reference of 1; R717 is ammonia, with essentially zero GWP. “Natural” does not mean safe to release or handle without precautions. Propane is highly flammable, CO2 can create serious pressure and exposure hazards, and ammonia has higher toxicity.

R22 is an HCFC containing chlorine. Its ozone-depleting-substance controls are separate from the HFC phase-down. Refrigerant numbers also include water and gases used in specialist low-temperature equipment; an unfamiliar refrigerant must be identified, not dismissed from its everyday use.

Reading a safety class

The letter indicates toxicity: A is lower, B is higher. The flammability part is separate:

  • 1: no flame propagation under the classification test conditions.
  • 2: lower flammability.
  • 2L: the lower-flammability subclass with low burning velocity.
  • 3: higher flammability.

R32 and R1234yf are A2L. Propane is A3. Ammonia is B2L. CO2 is A1, but concentrated CO2 can still harm health and displace breathable air. These classes tell you nothing about GWP or operating pressure, and they do not give a safe concentration for every situation.

Turning classification into precautions

Use the identified refrigerant’s properties together with charge size, equipment design and the surroundings. Suitable ventilation and detection reduce exposure risk; flammable gases also need ignition control, suitable tools and the specified charge and siting limits. Propane vapour can accumulate low down, but air movement and the release conditions affect its path. A smell, an open door or a quiet detector does not mean the area is safe.

Confirm the refrigerant from reliable labels and records before charging. Keep different recovered gases separate. Use the compressor and refrigerant manufacturer’s specified lubricant: compatibility, viscosity, moisture behaviour and oil return matter, and there is no single oil suitable for every system.

For zeotropic blends, follow the charging procedure, normally withdrawing liquid to retain the specified composition. Vapour withdrawal can change the proportions of the components. Use the specified dry oxygen-free nitrogen procedure for pressure testing; oxygen or compressed air can create hazardous reactions or contamination. OFN still requires pressure control and precautions against oxygen displacement.