Gas-fire safety checks and user handover: flue performance, carbon monoxide alarms, ignition, hearths and combustible shelf clearances.
Air and flue come first
An open-flued fire draws the air it burns from the room; its chimney or flue must take exhaust outdoors. It needs both: a clear, sound flue to remove the products and adequate ventilation to replace the air. Neither replaces the other. Too little replacement air raises the risk of incomplete combustion. Block or cap the flue, let an old unlined chimney leak, or run a strong extractor fan that lowers the room pressure, and products including CO can spill into the room or escape into voids and other rooms.
In the common balanced-flue version of a room-sealed heater, an enclosed path brings outdoor combustion air in and returns exhaust outside. Room-sealed systems also have other layouts; their defining feature is separation from occupied room air. Inspect the casing, seals and flue joints because failure can admit products indoors. A new gas appliance in a bath or shower room must be room-sealed.
A flueless heater releases combustion products and water vapour into the room. Meet its room and ventilation requirements and keep any required permanent vent clear. An openable window adds rapid ventilation to help remove products and moisture; it cannot replace the fixed air supply. See flueless-heater room and ventilation checks for the different appliance categories.
Hearth and clearances
- For a gas fire that needs a hearth, Approved Document J gives 12 mm as the minimum thickness of its non-combustible, non-friable top layer. Mark the hearth edge so combustible flooring is kept clear. The hearth may be omitted if the appliance instructions allow it, or if its flame and any incandescent material remain entirely at least 225 mm above the floor.
- Keep the manufacturer's clearances to mantelpieces, shelves, televisions and soft furnishings, which radiant and convected heat can scorch or ignite. A decorative fireguard does not replace them.
- Consider a fireguard for young children or less mobile occupants. It is a contact barrier only.
Commissioning and handover
- Check correct ignition and the flame pattern specified for that fire. Verify the required operating pressure and/or gas input at the prescribed test setting, and test flame-supervision shut-off within the specified response time. On an open-flued fire, also complete the required flue-flow and spillage tests; a good-looking flame does not mean combustion is safe.
- Show the user safe operation and the warning signs that mean stop using it: staining, unusual smells or a poor flame.
- Advise a CO alarm in the same room, sited to its instructions, and regular servicing by a competent person.
- If occupants feel unwell indoors and improve outside, act on possible CO exposure: move them into fresh air and seek prompt medical advice. Shut suspect appliances off if safe and keep people outside until advised they may return. The fire needs investigation before further use; severe symptoms call for emergency medical help.
- If smoke at the test point keeps returning after the specified warm-up and any permitted repeat, the spillage test has failed: do not leave the fire in use, and investigate and rectify the cause before it runs again.
Closure plate on an inset fire
Where a gas fire sits in a builder's opening, a closure plate seals that opening at its edges so the fire and its flue work correctly. It is not a flame guard, a gas isolation valve or a heat shield.
- Fit the size and type of plate the manufacturer specifies, sealed at its edges.
- Keep the spigot aperture and any specified relief opening clear: never blank them off or fit the wrong plate.
- An unsuitable plate or a blanked opening can upset the intended flue operation and allow products to spill into the room. Check the complete specified arrangement and test its performance.
What a gas fire or space heater is
A gas fire supplies warmth to the room where it is fitted, including a decorative fuel-effect model that also gives out heat. In a fire-and-back-boiler arrangement, the fire heats the room while the boiler circuit behind it heats water for radiators or taps.