Where main protective bonding connects at internal and external gas meters, what it does, and what to do if you find it missing.
What main protective bonding does
Main protective bonding is an electrical-safety measure for the installation pipework. It limits dangerous voltage differences between connected metalwork. It is separate from the circuit protective conductor in an appliance's electrical supply. It does not make the gas pipe a circuit conductor or an earth electrode, and it does not stop stray-current corrosion.
Is bonding needed?
Whether bonding is needed, and how big its conductor must be, is assessed under the electrical and installation requirements for the actual supply arrangement. Assess it each time: never use a cable size from memory.
- A metal pipe does not always bring in an external potential: assess it.
- An insulating incoming section can change the assessment, but other connections to Earth must still be considered.
- Check any extra requirements from the manufacturer of the installed pipework system.
- Do not remove an existing bond just because a visible plastic section seems to make it unnecessary.
Where the connection goes
For an internal meter, connect to suitable rigid metallic pipework on the consumer's side of the meter, before the first branch, and preferably within 600 mm of the meter outlet where practicable. That position gives one accessible connection before any branch, so later alterations to the branches cannot break it. Check continuity to every part that needs bonding: where the clamp sits does not show that.
For an external meter, the preferred position is near the point where the installation pipe enters the building. Do not carry the internal-meter 600 mm figure across to an external meter.
In every case:
- keep the connection accessible for inspection
- make it mechanically and electrically sound
- use the correct clamp or approved terminal for the pipework system; an ordinary clamp does not go directly onto flexible corrugated tubing
- never move the main connection onto the supplier's incoming pipe
If you find a defect
- Record that required bonding is missing, damaged or disconnected.
- Leave a bonding notice: written advice to the responsible person to have it checked and corrected by someone competent in electrical work.
- Do not improvise a permanent earth, and do not ignore the defect.
- If there is an immediate electrical danger, it needs the appropriate make-safe response; a note for later is not enough.
Being Gas Safe registered does not make you competent in electrical work. An engineer competent in both can do both, within that competence.
Exam cues
- Internal meter: consumer side, before any branch, preferably within 600 mm of the outlet where practicable.
- External meter: near the pipe's entry into the building.
- The purpose is electrical safety, not earthing the gas pipe or stopping corrosion.
- A gas operative without electrical competence records the defect and advises in writing; the repair is electrical work.