Meter and gas testing terms glossary

Note 9 of 12 · free to read

Plain definitions of the meter, pressure, testing and purging terms in MET1, with the formulas for gas rate, heat input and purge volume.

Controls and who looks after them

  • Emergency control valve (ECV) — the hand-operated valve upstream of the meter that shuts off gas to the whole installation. It must stay readily accessible and turn by hand.
  • Additional emergency control valve (AECV) — an additional emergency control in the installation, for example where occupants cannot readily reach the ECV. A tightness test from an AECV can have a different boundary from a test at the ECV.
  • Emergency notice — gives the emergency action and contact details at the meter or control. Operate the ECV only with safe access, then leave and call from a safe place.
  • Regulator (governor) — reduces and controls the supply pressure. Its seal protects the setting against interference: on a mains supply only the transporter, or someone authorised to act for it, may break it. A seal does not mean the pressure is right today. It is never adjusted to make an installation pass.
  • Gas transporter — on a typical network-supplied home, looks after the service up to and including the ECV.
  • Gas supplier — arranges meter matters. Installation pipework and appliances downstream are the owner's or landlord's responsibility.

Pressures and instruments

  • Standing pressure — pressure with no gas flowing.
  • Working pressure — pressure under the specified load.
  • Test pressure — the pressure the test method requires; it is not simply an appliance's operating pressure.
  • Test point — a small sealed tapping on the meter outlet or regulator where a gauge connects.
  • Manometer — the water or electronic gauge used for pressure and tightness tests. On a water U-gauge, the reading is the height difference between the two columns.

Tightness testing

  • Tightness (soundness) test — checks whether the section tested holds pressure under the specified conditions. A failure shows a loss from that section, not where it is.
  • Let-by — gas passing the closed valve relied on for isolation. The let-by check stops incoming gas masking a loss.
  • Stabilisation — the period before timing that lets temperature and pressure settle, so thermal effects are not read as a leak.
  • Perceptible movement — the Edition 4 benchmark. A perceptible fall fails a pipework test, and a connected test where appliances cannot reasonably be isolated must show no perceptible movement.
  • Permissible appliance loss — an allowance only for eligible existing appliances, assessed after the pipework is proved tight. It never permits pipework or meter leakage.
  • Leak detection fluid — an approved, non-corrosive fluid brushed or sprayed onto joints; a leak shows as growing bubbles. Wipe it off afterwards. Washing-up liquid is not an approved fluid.

Volumes and rates

  • Installation volume (IV) — the internal gas-holding volume of the section being tested or purged. A meter badge in m³/h is a flow rating, not this volume.
  • Purge volume (PV) — under Edition 4, PV = 1.5 × IV whenever purging is done.
  • Gas rate — the volume of gas an appliance uses per hour, in m³/h. For the volume used, read the meter index, time a set period with the appliance running, read it again and take end minus start.
  • Heat input — gas rate (m³/h) × calorific value (MJ/m³) ÷ 3.6 gives kW. Compare it with the data plate on the same gross or net basis.