Plain definitions of the meter, pressure, testing and purging terms in MET1, with the formulas for gas rate, heat input and purge volume.
Controls and who looks after them
- Emergency control valve (ECV) — the hand-operated valve upstream of the meter that shuts off gas to the whole installation. It must stay readily accessible and turn by hand.
- Additional emergency control valve (AECV) — an additional emergency control in the installation, for example where occupants cannot readily reach the ECV. A tightness test from an AECV can have a different boundary from a test at the ECV.
- Emergency notice — gives the emergency action and contact details at the meter or control. Operate the ECV only with safe access, then leave and call from a safe place.
- Regulator (governor) — reduces and controls the supply pressure. Its seal protects the setting against interference: on a mains supply only the transporter, or someone authorised to act for it, may break it. A seal does not mean the pressure is right today. It is never adjusted to make an installation pass.
- Gas transporter — on a typical network-supplied home, looks after the service up to and including the ECV.
- Gas supplier — arranges meter matters. Installation pipework and appliances downstream are the owner's or landlord's responsibility.
Pressures and instruments
- Standing pressure — pressure with no gas flowing.
- Working pressure — pressure under the specified load.
- Test pressure — the pressure the test method requires; it is not simply an appliance's operating pressure.
- Test point — a small sealed tapping on the meter outlet or regulator where a gauge connects.
- Manometer — the water or electronic gauge used for pressure and tightness tests. On a water U-gauge, the reading is the height difference between the two columns.
Tightness testing
- Tightness (soundness) test — checks whether the section tested holds pressure under the specified conditions. A failure shows a loss from that section, not where it is.
- Let-by — gas passing the closed valve relied on for isolation. The let-by check stops incoming gas masking a loss.
- Stabilisation — the period before timing that lets temperature and pressure settle, so thermal effects are not read as a leak.
- Perceptible movement — the Edition 4 benchmark. A perceptible fall fails a pipework test, and a connected test where appliances cannot reasonably be isolated must show no perceptible movement.
- Permissible appliance loss — an allowance only for eligible existing appliances, assessed after the pipework is proved tight. It never permits pipework or meter leakage.
- Leak detection fluid — an approved, non-corrosive fluid brushed or sprayed onto joints; a leak shows as growing bubbles. Wipe it off afterwards. Washing-up liquid is not an approved fluid.
Volumes and rates
- Installation volume (IV) — the internal gas-holding volume of the section being tested or purged. A meter badge in m³/h is a flow rating, not this volume.
- Purge volume (PV) — under Edition 4, PV = 1.5 × IV whenever purging is done.
- Gas rate — the volume of gas an appliance uses per hour, in m³/h. For the volume used, read the meter index, time a set period with the appliance running, read it again and take end minus start.
- Heat input — gas rate (m³/h) × calorific value (MJ/m³) ÷ 3.6 gives kW. Compare it with the data plate on the same gross or net basis.