The order of a domestic tightness test after meter work: set-up, let-by, stabilisation, the timed test, the Edition 4 result and what to do with a loss.

A soundness test checks whether the section under test is gas tight to the required standard. After a meter replacement, or pipework work that could affect tightness, test before the gas goes back into use. A suspected escape needs investigating and testing too. If air entered, test before the required purge. IGEM/UP/1B Edition 4 applies from 1 October 2026; Edition 3 was withdrawn on 30 September 2026.

Set up

  1. Define the test section. A normal test from the ECV includes the meter; a test from an AECV can have a different boundary.
  2. Connect a water or electronic manometer at the meter test point. On a water U-gauge, the reading is the height difference between the two columns.

The pipe between an appliance's isolation valve and the appliance is outside the pipework test. So before you isolate an appliance, plan how you will check that length when you restore it. If a check there with approved leak detection fluid is not practicable, keep that appliance connected for the pipework test and require no perceptible movement.

Protect the meter and check its internal valve

The Elster BK May 2026 instructions add component-specific checks to the applicable test procedure. Where a BK meter contains an integrated valve, that valve must be open for the tightness test. Left closed, it can cut the downstream pipework out of the section you are testing. No amount of extra pressure or time will fix that.

Compare any proposed test pressure with the meter's pmax. If the pipework test will go above it, the manufacturer requires the pipework to be tested before the meter is fitted. The meter and its connections then still need their own tightness checks. This higher-pressure case does not change the normal domestic test boundary, which includes the meter when you test from the ECV.

Apply pressure slowly, release test pressure slowly and follow the instructions when bringing the meter into service. These precautions do not change the pressure, time or permitted loss for the installation test.

On the BK's optional BS 4161 outlet test nipple, tell the removable test screw apart from the nipple itself. If the nipple comes loose, the manufacturer treats the meter as damaged and it must be replaced: tightening or resealing the nipple is not enough. After normal use of the test screw, close it as instructed and check the connection for tightness.

Let-by check

  1. Use the set let-by set-up and valve sequence to find out whether gas passes the closed control. Closing the handle is not the whole check: deal with trapped pressures and the test conditions too, or incoming gas could hide a loss downstream.
  2. If the pressure keeps rising after you have checked those, the isolation is probably passing. Confirm it and fix the cause by the procedure before you rely on the tightness result: an unexplained rise is not a pass.

Stabilise, then time the test

  1. Allow the stabilisation period so temperature and pressure settle; otherwise normal thermal effects can look like a leak.
  2. Time the test and watch the gauge. Smell or the meter index cannot prove tightness.

Judge the result

  1. Pipework and meter must be proved tight: a perceptible fall fails, and no appliance allowance applies.
  2. If a test with existing appliances connected loses pressure, isolate them where reasonably practicable and prove the pipework and meter tight first. Only then assess an eligible appliance loss against the fuel and volume limits, with no smell of gas.
  3. If appliances cannot reasonably be isolated, the connected test must show no perceptible movement.

If it fails

  1. Keep the supply off to the appliances. Brush approved leak detection fluid onto the joints, starting with those just disturbed, and watch for bubbles. Never use a naked flame.
  2. Make the affected section safe, remake the leaking joint and repeat the full test.
  3. A gas smell after a pass still needs investigating: find and rectify any escape, then retest. The smell does not tell you which part is leaking.

Finish

  1. Retighten the test point screw and check it with leak detection fluid.
  2. When restoring the appliance supplies, check disturbed joints and the previously excluded pipework between each appliance isolation valve and its appliance with approved leak-detection fluid.
  3. Purge where required, complete appliance checks, record the conditions and readings, and explain any restrictions to the responsible person.