How to pick out the ECV, the handover checks that let a user shut the gas off unaided, and the faults that defeat it.
The emergency control valve (ECV) is the hand-operated valve at or near the meter inlet that shuts off gas to the whole installation. A meter installation is arranged so the user can reach it and turn it, without tools, the moment they need to.
Pick it out
- The ECV is the valve with a handle on the inlet side, upstream of the regulator and meter.
- The sealed pressure device is the regulator, the used-gas display is the meter index, and the earth clamp is the bonding connection.
- On a lever-type ECV, the lever in line with the pipe means open and across the pipe means closed. A quarter turn shuts it. Where the lever moves vertically, its fully downward position must be closed.
A remotely operated meter valve has a separate role
Some Elster BK meters include a valve for remote connection and disconnection under the responsible operator's safe arrangements. The manufacturer states that it is not a safety shut-off valve. That internal valve is not the installation's automatic over-pressure protection, and it does not replace the accessible ECV: being electrically controlled and able to stop the flow does not make it a safety device.
Handover checks after work at the meter
- The key, lever or handwheel is securely attached and turns by hand.
- The label is in place, identifying the valve and showing on and off.
- The emergency notice is nearby, showing how to turn the gas off, what to do next and the gas emergency number.
- No pipework, bracket or stored item blocks access.
- A meter box door opens with its key, and the key is left with the occupier.
An ECV that only the engineer can operate has failed in its purpose.
Faults that defeat the ECV
- A handle painted over or seized so it cannot be turned by hand: do not force it; report it so the gas transporter or another authorised person repairs or replaces the valve.
- A missing handle or label: the user cannot rely on the valve in an emergency, so have it put right.
- Stored items blocking it, or a lost box key.
- An ECV in a locked communal riser that residents cannot reach: an additional emergency control valve (AECV) is provided where they can reach it.
In a suspected escape
Turn the ECV off only if you can reach it safely without entering the affected area, then leave and call the gas emergency service from a safe place. Never go into a cellar, basement or other affected area to reach it.