What the meter regulator does, the natural-gas pressures to know (21, 19 to 23 and 1 mbar), lock-up versus creep, and the seal, breather and OPSO.
Where it sits and what it does
Gas passes the service pipe, the ECV, the regulator (governor), the meter and then the installation pipework. The ECV is an on-off valve for isolation, the regulator controls pressure and the meter measures volume.
Network pressure varies with demand. The regulator is a self-acting valve: a diaphragm balanced against a spring opens it as outlet pressure falls and closes it as pressure rises, holding a set, lower outlet pressure as appliances light and go out. Without it, appliances could get unstable or excessive pressure, which upsets combustion.
Natural-gas figures
- About 21 mbar: nominal working pressure at the meter outlet.
- About 19 to 23 mbar: normal meter-outlet range, near 23 at low flow and near 19 at high flow.
- 1 mbar: maximum design loss from meter outlet to appliance inlet at maximum demand.
A nominal figure is not an exact pass mark, and LPG uses different figures. The 1 mbar is a design ceiling, not an assumed loss: compare meter-outlet and appliance-inlet readings at the same required load. Burner pressure is a separate measurement governed by the appliance’s design and controls.
Standing, working, lock-up, creep
Read these at the meter outlet test point, where the figures above apply.
- Standing: no gas flowing.
- Working: under the specified load, for example with the appliances the check requires running at full rate.
- Lock-up: the settled outlet pressure once demand stops and the regulator closes; it can sit above the working setting.
- Creep: a continued rise beyond the permitted lock-up range, with temperature and gauge setup checked, points to a passing regulator seat.
Reading the evidence
- Several appliances starved: check meter-outlet working pressure under load first. A good standing reading does not show the supply can meet the load.
- Meter outlet good but an appliance low: compare the appliance inlet at the same load and look downstream.
- Low settled standing pressure with a checked gauge: suspect the regulator or upstream supply, not pipework friction.
- Pressure too high: burners can over-gas, flames can lift or grow and incomplete combustion can produce carbon monoxide.
Seal, breather and OPSO
- The seal protects the setting against interference. On a mains supply only the transporter, or someone authorised to act for it, may break it, and a new seal must then be applied. A seal does not mean the pressure is right today, so measure it; report a fault to the gas emergency service, and never adjust the regulator yourself.
- The breather lets air move on the atmospheric side of the diaphragm. A failed diaphragm can pass gas, so a required vent pipe must end outdoors, away from ignition sources. Never plug it. Some models use an approved vent-limiting device; identify the regulator and follow its specified arrangement.
- An OPSO (slam-shut) trips closed at its over-pressure setting.
Electrical bonding near the meter
Main protective bonding is often connected to the installation pipework close to the meter. It is an electrical-safety measure: it limits dangerous voltage differences between metalwork if a fault occurs elsewhere in the property's wiring. It does not make the gas pipe an earth electrode, play any part in regulating pressure, or stop stray-current corrosion. Whether bonding is needed, and its conductor size, is decided under the applicable electrical requirements, not by a fixed rule at the meter.