Rainwater system design: gutter types, falls and bracket spacing

Note 2 of 7 · free to read

Gutter profiles, manufacturer-specific falls and support centres, with effective roof area and safe discharge checks.

A rainwater system collects the water that runs off a roof and takes it safely to a surface water drain or soakaway. That protects the building's fabric. In England, follow Approved Document H, Part H3 for the drainage guidance, together with the instructions for the system you install.

Gutter Profiles

  • Half-Round: a common domestic profile. Check its rated capacity for the roof area it drains and the outlet layout.
  • Square-Line: another common profile. Check its actual capacity; the name does not tell you.
  • Deep-Flow: a deeper section, which can carry more water from a large roof. Compare the capacity and outlet layout of the profile you choose.
  • Parapet or Box Gutters: built into the roof structure, not hung at the open eaves. If their outlets cannot cope or get blocked, the water backs up and can get into the building. They need outlets big enough for the flow, and often an overflow as well.

Setting Falls (Gradients)

Follow the installation and capacity instructions for the system you install. A gutter can be laid level and still have a valid design capacity. Where a fall is specified, set it towards the outlet, and keep the gutter where it catches the water from the roof edge. A sag in one place is a fault, not a level run.

  • Worked gradient: 1 in 600 means a 1 mm drop in every 600 mm of horizontal run, about 1.7 mm per metre. Over 6 metres the drop is 6000 ÷ 600 = 10 mm. This shows the conversion; it is not a minimum fall.
  • Manufacturer examples: FloPlast’s cited PVCu instructions recommend 1 in 350. Alumasc’s Apex cast-iron guide specifies a fall from 1 in 600 to 1 in 350, or level where that is not possible. Follow the instructions and rated layout for your profile.

Gutter Bracket Support Spacing

Brackets must hold the gutter when it is full and keep it on its designed line. The bracket centres depend on the profile, the fixings, the fascia, the water and snow load, and the manufacturer’s instructions. A heavier material does not always need closer brackets than a plastic system.

For the cited FloPlast PVCu systems:

  • On straight runs, fascia brackets go at no more than 1.0 metre, or 800 mm for Niagara and 600 mm for Xtraflo.
  • With an 80 mm round downpipe on Hi-Cap or Niagara, the guide gives 800 mm maximum fascia-bracket spacing.
  • Where high snowfall is possible, the maximum is 400 mm.
  • Fit a fascia bracket within 150 mm of angles and stop ends. Fix unions, outlets and other fittings as their own instructions say; the 150 mm rule does not cover every fitting.
  • Support downpipes below an offset and at no more than 1.8 metres in this system. Support shoes, branches and bends where needed.

Alumasc’s cited Apex cast-iron gutter guide generally uses 915 mm centres, with extra support at the gutter joints. Each figure belongs to its own system: do not swap them between systems.

Roof Area and Flow Capacity

The gutter and downpipe sizes depend on the effective roof area, which allows for the roof's pitch. Approved Document H multiplies each pitched slope's plan area by a set factor:

  • 1.29 at 30 degrees
  • 1.50 at 45 degrees
  • 1.87 at 60 degrees

A flat roof keeps its plan area. A wall, or a roof pitched over 70 degrees, counts as half its elevational area.

Positioning, discharge and soakaways

Set the gutter under the edge of the roof covering, so it catches the water as it comes off the tiles. Set too low or too far back, a gutter lets heavy rain jump straight over it.

Take the discharge to a proper gully, drain or soakaway. Do not let it fall at the wall or across a path:

  • against the foundations, it soaks the ground beneath them and can cause damp or erosion;
  • across a path, it can freeze into a slip hazard.

A soakaway needs:

  • ground permeable enough to accept the water;
  • the water table below its base;
  • a distance of at least 5 metres from a building or road.

For a small soakaway serving 25 square metres or less, Approved Document H allows an assumed design storm of 10 mm of rain in 5 minutes in its small-soakaway method. You still need to check the ground and use the right sizing method. No design storm covers every possible storm.