Hot Water Systems

Stored water temperature and Legionella awareness

Note 3 of 11 · free to read

Why hot water is stored hot and cold kept cold, and how dead legs and stagnation raise bacterial risk.

Hot water systems carry two opposite risks that have to be balanced: scalding from water that is too hot, and bacterial growth in water that is too warm and too still. Understanding the temperature picture is core revision.

Legionella and similar bacteria multiply in warm, stagnant water, broadly in the range from about 20 to 45 °C. Under the conventional temperature-control regime, store hot water at 60 °C or more, distribute it so the unblended hot supply reaches 50 °C within one minute at outlets (55 °C in healthcare premises), and keep cold water below 20 °C where possible. In a vented system, expansion water passes back up the cold feed into the storage cistern; where that cistern also supplies the cold taps, Water Regs UK's guidance says the expansion water should not raise it above 25 °C in England and Wales (20 °C in Scotland and Northern Ireland). A combination unit, with its cold store built above the hot vessel, may let heat reach the cold water. HSG274 Part 2 notes that the regulations and BS 3198 permit up to 25 °C in that cold store where it serves other domestic outlets, or 38 °C where it serves only the hot water vessel. Check the hot supply before any mixing valve; its cooler outlet has a separate scald-protection purpose.

Stagnation makes it worse. A branch that only flows when its outlet opens is one meaning of a dead leg; the term is also used for redundant or little-used pipework. A branch you need is not a defect in itself, but if it is rarely used its water can sit warm and still for long periods. Warmth, poor turnover and deposits all help bacteria grow.

Remove redundant pipework back to the live connection, keep necessary branches short and manage infrequently used outlets. Insulation slows heat transfer, but it cannot keep unused water at a safe temperature for ever. Check temperatures and keep the water moving as part of the hygiene controls.

The apparent conflict with scald safety is resolved by storing water hot but delivering it blended down at the tap, for example through a thermostatic mixing valve, so what reaches the user is safe to touch.

This is safety-critical. For a real risk assessment and control of bacteria in water systems, follow the public health guidance and the current Part G, not memory.

Secondary circulation and the remaining branches

A secondary loop keeps hot water near distant outlets and returns it to the store. It needs suitable insulation, balancing and temperature control. The short branches from the loop to the taps still need turnover: running the circulation pump does not flush an unused outlet. Remove redundant dead ends, manage rarely used outlets and check the temperatures: circulation alone does not control Legionella.

Vessels, expansion vessels and small heaters

HSE's HSG274 Part 2 names the base of a water heater or storage vessel as a risk area: incoming cold water lowers the temperature there, and sediment collects there and is carried round the system. Its checklist asks for the first flush from the base of a hot water heater to be drained off and inspected each year for clarity, debris and temperature, so the drain valve should be easy to reach.

An expansion vessel on a system running at a steady temperature and pressure can go long periods without exchanging much water. HSG274 asks for it to be fitted in a cool place on a cold flowing pipe, as close to the incoming supply as possible, mounted vertically to limit trapped debris, with an isolation and drain valve, and holding as little water as it can. Its bladder, often EPDM rubber, can support microbial growth, so check it is approved to BS 6920. A flow-through design gives the water less chance to stagnate. HSG274's checklist also asks for expansion vessels to be flushed through and purged to drain, where practical, every one to six months as the risk assessment indicates, with bladders changed as the manufacturer advises.

Low storage volume heaters, holding no more than 15 litres, such as instantaneous and point-of-use units, may generally be regarded as lower risk. They should still be able to reach 50 to 60 °C, and users should be told not to adjust them. One that is rarely used, set to give only warm water, or fed from a cold water storage tank carries far more risk.

Showers and spray outlets

Showers turn water into a fine spray that can be breathed in. HSG274 Part 2's checklist asks for shower heads, inserts and hoses, and the spray nozzles of electric showers and other small heaters, to be dismantled, cleaned and descaled quarterly, or more often where the rate of fouling or the users call for it. Consider removing showers and taps that are seldom used, cutting their pipework back to a common supply. Where they stay, flushing them weekly for several minutes, and logging it, greatly reduces the legionella risk.

Where the monthly checks are taken

HSG274 Part 2 has hot water temperatures checked at sentinel outlets, chosen so that a few readings show how the whole system is doing. In a simple system with no circulation loop, the near and far sentinels are the taps nearest to and furthest from the water heater, and the ends of significant branches count as extra far sentinels. In a circulating system, the far sentinels are the return legs towards the end of each loop. Pick them from the pipework layout, which may not match where the taps sit in the building. Each month the hot water at them should reach at least 50 °C (55 °C in healthcare premises), within one minute of running at a tap. For cold water, the sentinels are the taps nearest to and furthest from the supply or storage tank.