Worked high- and low-vent sizes for an open-flued boiler in a cupboard, vented into a room or direct to outside, and the checks before relying on them.
An open-flued boiler in a cupboard takes its combustion air from the cupboard, and the cupboard also has to shed the heat the boiler gives off. So it needs two openings: a low one where cooler air enters and a high one where warmed air leaves. Check each opening separately: adding the two areas together tells you nothing, and the two are not always equal.
The rates depend on where the openings lead. For an open-flued appliance in a compartment, Approved Document J gives, per kW of net input:
- Openings direct to outside: 5 cm² high and 10 cm² low.
- Openings into an adjoining room: double, 10 cm² high and 20 cm² low. That room then needs its own vent to outside at 5 cm² per kW, with the first 7 kW deductible only where the older-dwelling air-permeability condition allows it. The compartment openings always use the full input.
Example 1: 24 kW net boiler, compartment vented into a room
Assume the room does not qualify for the 7 kW allowance.
- Low opening: 24 kW × 20 cm²/kW = 480 cm².
- High opening: 24 kW × 10 cm²/kW = 240 cm².
- Room vent to outside: 24 kW × 5 cm²/kW = 120 cm². Without it, the air path ends inside the building.
Example 2: same boiler, compartment vented direct to outside
- Low opening: 24 kW × 10 cm²/kW = 240 cm².
- High opening: 24 kW × 5 cm²/kW = 120 cm².
- In square millimetres, multiply by 100: 240 cm² = 24,000 mm².
Before you rely on the numbers
- Confirm the figure applies to this appliance type and this arrangement. A correct value from the wrong table can still leave the appliance short of air.
- A room-sealed boiler in a cupboard takes its combustion air from outside. Whether the cupboard needs cooling vents depends on the boiler's instructions and the clearances; some need none.
- Do not deduct a room's 7 kW allowance from compartment openings.
- Choose ventilators by their declared equivalent area, not the frame size. Keep them permanently open: a vent the user can cover is not a permanent vent.