Safe termination options for unvented cylinder discharge pipework

Note 3 of 10 · free to read

Where D2 can end: a guarded outlet over hardstanding, a trapped gully, a suitable soil stack or at high level, and the terminations that fail.

An unvented cylinder's relief discharge can be very hot water and steam, arriving at the outlet close to the stored water temperature. Provide a termination that avoids scalding and damage, and keep discharge visible at the tundish so an unexpected release can be noticed. An intentional service test is a different context from an unexplained discharge. Approved Document G describes several arrangements for England; low level is common but not a universal requirement. The cylinder and discharge-system instructions also apply.

External hardstanding

For a downward outlet above external hardstanding, finish no more than 100 mm above the surface. Fit a wire cage or similar guard so nobody can touch the discharge while it stays visible. Choose a position where hot water cannot injure someone or create an access hazard.

Trapped gully

Place the outlet below a fixed grating and above the water seal. The 100 mm hardstanding rule does not apply here: this is a different arrangement. Keep the outlet clear so the discharge can escape.

High level

Two high-level options are described:

  • Into a metal hopper and metal downpipe, with the end of the discharge pipe clearly visible.
  • Onto a roof that can withstand near-boiling water, at least 3 m from any plastic guttering that would collect the discharge. Hot water and steam damage plastic rainwater goods, asphalt and roofing felt.

Internal soil stack

An internal connection is not automatically prohibited, but it is a specified arrangement. The stack must withstand the discharge temperature, with a separate branch serving no sanitary appliances, the required warning marking and a mechanical odour seal without a water trap. Any plastic pipework must meet the stated performance requirements; an ordinary waste connection is not enough. Verify the complete arrangement before using it, and keep the discharge visible at the tundish.

Terminations that fail

  • Just above a doorway step where people stand: someone could be scalded.
  • An open end in a concealed wall void or cupboard: with no protected collection or drain connection, it can scald or flood unseen and it hides the warning. On a service, record it as non-compliant and require a safe termination with discharge visible at the tundish.
  • A route that rises before it falls: after the tundish's air break, D2 relies on gravity and needs a continuous fall. A larger diameter does not fix it.
  • Any isolating or shut-off valve on the discharge: even one meant only for servicing would, once closed, stop the relief valve discharging.

A concealed section of D2 is not automatically a defect, provided the tundish stays visible and the pipe is still sized, falls and terminates correctly. If no safe discharge route with a visible tundish warning can be provided, do not go ahead with the installation until one is resolved.