The ventilation a kitchen needs for a gas cooker: an openable window, a permanent vent by room volume, and what does not count.
Why the room matters
A conventional flueless domestic cooker has no dedicated external flue. Its oven or grill can still have internal passages and an outlet into the kitchen, which must remain clear. It burns room air and releases its products into the kitchen: carbon dioxide and water vapour even when burning perfectly, and CO if combustion goes wrong. The room must provide enough fresh air for combustion and a way to clear the products. The burners, assembly and gas settings must also be correct: good ventilation alone does not make a cooker safe.
The ventilation rules
A room containing one of these flueless cookers needs an openable window or equivalent for rapid ventilation. For the conventional flueless cookers covered here, the usual room-volume bands for a permanent, non-closable vent are:
- under 5 m³: 100 cm²
- 5 to 10 m³: 50 cm², unless the room has a door opening directly to outside
- over 10 m³: no permanent vent
Example: an 8 m³ kitchen with an openable window but no outside door needs a 50 cm² permanent vent. A permanent vent matters in a small room because a window depends on someone opening it.
A room with a gas point intended for a flueless appliance, such as a cooker point, gets that ventilation before any appliance is chosen. It is sized as if the largest appliance rating the ventilation table allows were installed (Approved Document J, paragraph 3.16).
Do not install a cooker in a bed-sitting room smaller than 20 m³, or in a room containing a bath or shower. Check the particular cooker’s instructions and any other fuel-burning appliances in the room before applying these bands. A conventional flueless range follows its cooker requirements; do not use this table for a different appliance type such as a flued heat-storage range.
What undermines it
- Blocked or taped vents: the cooker loses combustion air, risking incomplete combustion and CO.
- Recirculating hood: it filters air and returns it to the room, so it does not exhaust the products outside.
- Powerful extractor with an open-flued appliance in the same room: check for spillage under the prescribed combinations of extract fans and internal doors. The required adverse test condition may involve more than switching on one fan.
- Long operation in a poorly ventilated kitchen: the burners consume room air. If fresh air cannot replace it, combustion can become incomplete and produce CO; moisture and other products may also remain in the room.
- Using the cooker to heat the room: it is not designed or flued for space heating.