LPG storage: cylinder and bulk tank siting

Note 9 of 12 · free to read

Siting LPG cylinders and bulk tanks safely, allowing for a gas that is heavier than air.

Siting LPG safely

LPG is stored as a liquid under pressure and turns to gas as it is drawn off. Because LPG vapour is denser than air, safe siting is built around keeping any leak away from places where it could collect or find an ignition source.

Keep leaks away from low places

Escaping LPG vapour can collect in low or enclosed places. Keep the specified separation from drains, gullies, cellars and other below-ground openings, and provide the designed ventilation. Outdoor siting helps dispersal but does not guarantee that a leak is safe: release conditions, wind and obstructions still matter. Above-ground and underground bulk tanks have different installation arrangements.

Cylinders and bulk tanks

  • Cylinders are stored upright on a firm, level base in the open air, away from doors, windows, drains and sources of heat or ignition.
  • Bulk tanks sit on a firm, level base with clear separation from buildings, boundaries and ignition sources, and with no combustible material stored nearby.

Clearances

Minimum separation and clearance distances apply to both cylinders and bulk tanks, and they depend on the size of the store and the surroundings. Treat any distance you remember as a guide only and verify the current figures against the gas supplier guidance, the LPG industry rules and Building Regulations before you site a store.

Confirm siting, clearances and ventilation against current LPG and Building Regulations guidance.

The figures in Approved Document J for England

  • Bulk tanks: Table 11 covers one tank standing in the open, up to 1.1 tonnes. Without a fire wall, separation from buildings, boundaries and fixed ignition sources is at least 2.5 m up to 0.25 tonne, or 3 m above 0.25 and up to 1.1 tonnes. A compliant shielding wall permits direct clearances of 0.3 m and 1.5 m respectively, but the unshielded distance must still be maintained around or to the wall ends as specified. The wall reaches at least the pressure-relief-valve height, uses the required imperforate construction and fire resistance, and preserves ventilation. A building wall used as the fire wall has additional conditions. Protect drains, gullies and cellar hatches within the separation distance against gas entry.
  • Cylinders: they stand upright, secured by straps or chains against an outside wall, at ground level in a well-ventilated position, protected from damage and not obstructing an exit. The base is firm and level, such as concrete at least 50 mm thick.
  • Cylinder valves: at least 1 m horizontally and 300 mm vertically from openings into the building and from heat sources such as flue terminals and tumble-dryer vents. At least 2 m horizontally from untrapped drains, unsealed gullies and cellar hatches, unless a wall at least 250 mm high stands between them.
  • Keep ignition sources outside the specified separation: a flammable mixture may form near a leak or where the vapour travels.