An ordered set of checks for the common complaint of a combination boiler giving heating but no hot water, or none at all.
No hot water is one of the most common call-outs. Work from simple and external to internal and complex, and follow the manufacturer's fault-finding guide for the exact appliance.
- Get the story. No hot water at all, heating but no hot water, or only lukewarm? Did it stop suddenly or fade? Identify whether it is an instantaneous or a storage combi before following its hot-water circuit.
- Check the basics. Confirm the boiler has power, the gas is on and the system pressure is in range, and read any fault code before touching anything.
- Use the heating as evidence. Warm radiators show that the boiler fires and circulates water on a heating call. A total loss of power or gas is less likely, but a hot-water call and its flow path still need their own checks.
- Check the demand. On an instantaneous combi, confirm the appliance registers a hot-water draw-off. A flow sensor or flow switch fault can stop the demand while heating still works. A storage combi also has a store-charging circuit and controls to check.
- Check the path. Where the design uses a diverter valve and a separate plate heat exchanger, check that the valve moves to the hot-water position and that heat transfers, using the prescribed tests. Lukewarm hot water with normal heating points to diverter movement, flow detection or a scaled or blocked plate heat exchanger. These are possible causes; the symptom does not tell you which.
- Check the temperature controls. Confirm the hot-water setting and any thermistor reading are sensible; a faulty sensor can make the boiler behave oddly.
- Confirm combustion and safety. If it fires for hot water, confirm it is gassing and burning correctly and that the safety devices work.
- Prove and recommission. After a repair, prove the fix, recheck combustion and the controls, and leave the appliance working correctly.
Compare: stored hot water
With a separate cylinder, trace its call for heat through the programmer and cylinder thermostat. In S-plan, check the hot-water zone valve; in Y-plan, check the mid-position valve. Confirm primary water can reach the cylinder coil. Radiators heating makes a total loss of heat or circulation less likely, but it does not clear the shared parts that work on the cylinder call.