Why metal pipework is bonded, what main and supplementary bonding do, and why a plumber must not remove it.
Why pipework matters electrically
Metal pipe can form part of a building’s protective bonding system or provide another route for electrical current. Cutting or removing it may interrupt that route, even though the plumbing work itself is sound.
Main protective bonding connects extraneous-conductive-parts to the main earthing terminal. These are parts outside the electrical installation that can introduce a potential, usually earth potential. An incoming metal service may qualify; a fitting does not qualify just because it is metal. A plastic incoming service changes the assessment, but other earth connections must still be considered. Copper fed from a plastic service can itself leave the building and go into the ground, for example in a buried run to an outbuilding, and so bring earth potential in. Find out where the metalwork goes before deciding it needs no bonding; the decision rests with the installation's designer.
Bonding reduces dangerous voltage differences between connected parts a person could touch together. It does not keep every part at zero volts, and a fault can still produce a dangerous touch voltage. Supplementary bonding is an additional local measure with its own requirements.
What does and does not need bonding
A kitchen sink needs no bonding. A kitchen is not a special location, and the sink is a separate piece of metal that cannot bring in a potential from anywhere, so the green-and-yellow link often found between a sink's tag and its pipes is not required. An oil tank in the garden is not an extraneous-conductive-part either, despite the earth rods often seen beside tanks; a metal oil pipe coming in from the ground can be, so it is bonded as close as practicable to where it enters the building, preferably within 600 mm and before any branch. Supplementary bonding is usually needed only in special locations, such as a room with a bath or shower, and BS 7671:2018 lets even that be left out where Regulation 701.415.2 is met, chiefly where the circuits are RCD protected and main protective bonding is in place. Many older homes have bonding on baths, radiators, taps and tanks because the 15th Edition of the Wiring Regulations (1981) asked for it; since the 16th Edition (1991), only extraneous-conductive-parts need bonding. Existing bonding is still never simply removed: have it assessed by a competent electrician. BS 7671:2018 also says a metal pipe with an insulating section at its point of entry need not be connected to the protective bonding, though metalwork that leaves the building elsewhere, or meets the ground or earthed plant, can still bring Earth potential in.
Before cutting or replacing pipe
Plan how the required electrical continuity will be maintained. A plastic insert can interrupt a previously continuous metal path. Existing bonding must not simply be removed or left disconnected; have the arrangement assessed and any required repair made and verified by a person competent in that electrical work.
Where the work requires a temporary continuity link, fit it across the intended break before opening the pipe, with effective contacts. It is not the permanent bond, and it does not replace the gas-work precautions or an assessment of the electrical hazards. Protective and bonding conductors can carry current, including neutral current diverted from elsewhere, even with the property’s main switch off. If you find signs of dangerous voltage or current, stop and get competent help. Sparks as a pipe joint is undone can be neutral current diversion, from a broken PEN conductor on a TN-C-S (PME) supply: the IET and its industry partners advise reporting a suspected case to the local network operator without delay, by calling 105.
Fit the temporary bond before the pipe is opened, with a clip on clean, bare metal on each side of the cut, so that it bridges the gap: paint or corrosion under a clip can stop it making contact. Leave it on until the pipework is joined again and any permanent bonding has been restored.
What the CPC does
A Class I appliance’s circuit protective conductor provides the intended path for fault current, allowing its protective device to disconnect within the required time. It is not the circuit’s normal load return, but equipment leakage or functional currents can flow through it in normal operation.
A loose or broken CPC can leave a metal case live if a fault happens. The appliance can carry on working, so working tells you nothing about the protective path. An RCD, or another path that happens to exist, never makes up for a missing CPC.
Green-and-yellow insulation shows what the conductor is for, not that it is connected correctly: continuity and the connections need checking. The assessment and the work need electrical competence; a plumbing repair does not certify electrical safety.
Class II and the double square
Equipment marked with two concentric squares is Class II. It relies on double or reinforced insulation, so if the basic insulation fails a second layer still keeps the user away from live parts, and it has no provision for an earth connection. There is no agreed symbol for Class I, and a plastic case alone does not prove an appliance is Class II. The double square says nothing about water: protection against water is shown by the IP rating.
Earthing systems
How an installation gets its earth depends on the supply. In a TT system the network operator provides no earth terminal, and the installation is earthed through its own electrode at the property, usually a rod; it relies on RCDs to disconnect earth faults, because the electrode's resistance is too high for fuses or circuit-breakers to clear them quickly. In TN-S the earth comes from a separate protective conductor in the supply cable, often its metal sheath. In TN-C-S, known as PME, the supply combines neutral and earth in one conductor, and the installation's earth is taken from it at the intake.