Hot Water (L3)

Cylinder reheat and recovery time (worked example)

Note 4 of 12 · free to read

Using the useful heat input to estimate recovery time, then checking actual cylinder performance.

How fast does the store recover

Recovery or reheat time tells you how quickly a cylinder is ready again after a big draw-off. The method is the same energy idea as before: find the energy needed, then divide by the heat input power. The numbers here are chosen to show the method.

The situation. A 120 litre cylinder (about 120 kg of water) needs a 45 °C temperature rise back to 60 °C. For this calculation, assume the coil supplies an average useful input of 10 kW to the water over that period and ignore heat losses.

Step 1 - energy required. Q = m x c x change in T = 120 x 4.186 x 45 = 22,604 kJ, about 22.6 megajoules.

Step 2 - reheat time. A 10 kW coil delivers 10 kJ each second. Time = 22,604 / 10 = 2260 seconds, which is about 38 minutes.

Compare with an immersion. The same job on a 3 kW immersion would take 22,604 / 3 = about 7535 seconds, or roughly 126 minutes. The shorter time follows from the assumed 10 kW useful input compared with 3 kW for the same heating task.

Real life. A coil’s transferred power changes with primary and stored-water temperatures, flow and available heat-source output. Use its performance at the actual conditions, with the relevant heat losses and control operation. Do not apply a second arbitrary coil-efficiency penalty after already using useful heat transferred to the water, or assume the real time is only slightly longer. Compare the manufacturer’s recovery data with the demand pattern.