Things to check so a sanitary appliance drains properly and keeps its water seal against smells.
For an appliance using a conventional water-sealed trap, check both the seal and the branch arrangement when you investigate smells or poor drainage. Here is what to check; take the figures from Approved Document H.
- Check the trap matches the appliance and has the correct seal depth, because too shallow a seal is easily lost.
- Keep the branch pipe length within the limit for its diameter; over-long branches are prone to self-siphonage that empties the trap.
- Set the branch gradient within the allowed range so it drains fully without sucking the seal out behind the flow.
- Position the connection into the stack so one appliance discharging does not siphon or back-pressure another appliance’s trap.
- Provide the branch ventilation required by the design. A suitable AAV can admit air against suction, but cannot relieve positive pressure; an open vent provides airflow in both directions.
- Make sure the trap is accessible for cleaning and that there are no sags in flexible waste pipe that could hold water and debris.
The aim is always the same: water flows away and the seal stays put. Check seal depths, branch lengths and gradients for each appliance and pipe size in Part H.
Bends, junctions and joints
Lay bends and junctions with as large a radius as possible and swept in the direction of flow, so waste turns smoothly instead of catching and building a blockage. Keep every mechanical joint - including a boss connection into the stack - properly made and airtight; a loose joint lets drain air escape into the room even when nothing is actually blocked.
Testing the pipework
Approved Document H asks for the pipes, fittings and joints of above-ground sanitary pipework to withstand an air test at a positive pressure of at least 38 mm water gauge for at least 3 minutes, with every trap keeping a water seal of at least 25 mm. Where a water test has failed, smoke testing may be used to find the defect, but it is not recommended for PVC-U pipes.