PlumbRevise
Cold Water (L3)

Flushing and disinfection (PD 855468 overview)

Note 10 of 12 · free to read

An overview of flushing and disinfecting a cold water system to PD 855468 principles.

Why flush and disinfect

A new or altered cold water system can carry swarf, flux, dust and other contamination from installation. Flushing removes loose debris. Where disinfection is required, carry out and validate the specified process to control microbial contamination before the system is used. PD 855468 is the UK guide covering the flushing and disinfection of services supplying water for domestic use within buildings.

The principle

  • Flush the system thoroughly first, so disinfection acts on clean surfaces rather than on debris.
  • Disinfect when required, commonly with a chlorine-based product. Bring the treatment through the system and monitor it at the specified points so the required concentration is maintained for the full contact period. A dose added at one point may not reach the whole system.
  • After the contact period, flush the disinfectant out until residual levels are acceptable, then confirm the water is satisfactory.
  • Record the concentration measurements, timing, final flushing and validation results. These let the completed process be checked; written entries do not replace the actual measurements or confirmation that the water is satisfactory.

When it is needed

New or altered systems need appropriate cleaning and flushing. Determine whether disinfection is necessary from the applicable requirements, commissioning specification and risk assessment, including after contamination or work on storage. Validate the completed process before putting the water into service.

Disinfection chemicals are hazardous and the concentrations and contact times matter, so do not rely on remembered figures: follow PD 855468, the chemical manufacturer instructions and any project specification, and test the result.