Keeping cold water cool, moving and clean to control Legionella.
The control idea
Legionella bacteria thrive in stagnant water roughly between 20°C and 45°C and in systems holding debris and biofilm. Control in cold water systems rests on three ideas: keep the water cool, below 20°C where practical; keep it moving, avoiding stagnation; and keep it clean.
Practical measures
- Temperature: keep cold storage and distribution below 20°C, insulating and routing pipes away from heat.
- Turnover: size storage so water turns over and does not sit for days, avoiding grossly oversized cisterns.
- Dead legs: design out blind ends and redundant branches where water stagnates, and remove pipework left after alterations.
- Use: flush infrequently used outlets regularly so water does not stand in them.
- Cleanliness: keep suitable covers and screens intact to limit contamination entering the cistern, and inspect and clean as needed. Siting, insulation and turnover keep the water cool; a cover does not.
Responsibility
Those who manage premises have duties to assess and control the risk. HSE guidance, the L8 Approved Code of Practice and HSG274, sets out the approach and is the reference for control measures and monitoring.
This is safety-critical: confirm control measures, temperatures and frequencies against HSE L8 and HSG274 and BS 8558.
Outlets and dead legs
- Showers and spray taps produce a fine spray that people breathe in, and scale and biofilm in the head and hose shelter bacteria. That is why they are cleaned and descaled on a routine rather than only when the spray pattern suffers.
- Remove a redundant branch back to the live pipework rather than capping it: a cap leaves a dead leg of standing water that warms and supports growth.
- Stored water that stands too long deteriorates, so match cistern and break tank volumes to realistic demand.