What the Water Fittings Regulations require and which cold water work must be notified in advance.
The Regulations
In England and Wales, the Water Supply (Water Fittings) Regulations 1999 set out to prevent waste, misuse, undue consumption, contamination and erroneous measurement of water supplied by a water undertaker. Scotland and Northern Ireland have their own applicable rules. Use the rules for the location: fittings must be suitable, correctly installed and protected against the relevant backflow risks.
Notification
Some work is notifiable, which means the water undertaker must be told in advance so the proposals can be checked before the work is connected. Notifiable items include the specified new work and fittings in Regulation 5. Check the exact list and any approved-contractor exception: storage arrangements and pumps do not all carry the same duty. Giving notice lets the undertaker confirm there is adequate backflow protection and no risk to the public supply.
Where Approved Document G fits
In England, Part G of the Building Regulations sets requirements for water supply, water efficiency and hot water safety. Approved Document G is statutory guidance on meeting those requirements; another compliant approach is possible. The installation must meet the applicable Part G requirements and the Water Fittings Regulations. Following one does not waive the other.
Before relying on this overview, check exactly which items are notifiable, and the current requirements, in the Regulations and current WaterRegsUK guidance.
Notifiable work in detail
Regulation 5 lists the work that needs notice to the water undertaker, and its consent, before it starts. The list includes:
- erecting a building or other structure, other than a pond or swimming pool;
- extending or altering the water system in premises other than a house, or a material change of use;
- a bath holding more than 230 litres, measured to the centre line of the overflow;
- a bidet with an ascending spray or flexible hose;
- a pump or booster drawing more than 12 litres a minute from a supply pipe, directly or indirectly;
- a reverse osmosis unit, or a water treatment unit that discharges waste water or uses water to regenerate or clean;
- a reduced pressure zone valve or other mechanical device protecting against a category 4 or 5 fluid;
- a garden watering system not operated by hand, and pipe laid outside a building less than 750 mm or more than 1,350 mm below ground;
- a pond or swimming pool of more than 10,000 litres that is filled automatically from the supply.
The undertaker may refuse consent, or grant it with conditions, by notice within ten working days of the day the notice was given. If it says nothing in that time, consent is treated as granted without conditions. An approved contractor does not need to notify three of these items: altering a system in premises other than a house, the bidet, and the category 4 or 5 device.
An approved contractor gives the person who commissioned the work a signed certificate stating whether it complies, and for notifiable work sends a copy to the water undertaker. The water undertaker enforces the Regulations. Part G of the Building Regulations and the Water Fittings Regulations both apply to the same installation, so it has to satisfy both.
Water efficiency limits
A flushing device installed for a WC pan must not give a single flush of more than 6 litres. On a dual-flush device, the smaller flush must be no more than two-thirds of the larger. A cistern installed before 1 July 1999 may be replaced by one giving a similar volume. Every flushing cistern is marked inside with a line showing the intended flush volume.
Backflow protection follows the fluid category
The Regulations group fluids into five categories by the risk they pose to health:
- Category 1: wholesome water as supplied by the water undertaker.
- Category 2: wholesome water whose taste, smell, appearance or temperature has changed, such as water in a hot water system.
- Category 3: a slight health hazard from substances of low toxicity, such as ethylene glycol or common disinfectants.
- Category 4: a significant health hazard from toxic substances, such as pesticides or carcinogenic chemicals.
- Category 5: a serious health hazard from pathogens, human or animal waste, or very toxic substances.
Choose the device from the category, never from what happens to fit. A single check valve protects up to category 2, a double check valve up to category 3, a reduced pressure zone (RPZ) valve up to category 4, and an AA or AB air gap up to category 5. Check which forms of backflow can occur as well. Back-siphonage happens when the supply pressure falls and the system draws water back. Back-pressure happens when something downstream, such as a pump, a heated system or a head of water, is at a higher pressure than the supply and pushes water back. Where back-pressure can occur, do not use an arrangement approved only for back-siphonage: it must suit the assessed mechanism as well as the fluid category.
- A hose from a hose union tap can be left lying in a water butt, bucket or pond, so the tap needs backflow protection suited to that risk.
- A booster pump can create back-pressure towards the main, so protection is needed at its supply connection.
- A temporary filling hose between the supply and a heating circuit carries the right protection and is disconnected once filling is finished; left in place it is a cross-connection.
- The relief outlet of a BA or CA device discharges through an air gap, so its discharge stays clear of the drain.
- Backflow devices stay accessible for inspection, maintenance and replacement.
- Every fitting in contact with wholesome water must be suitable for it. Keep the approval listing or manufacturer's declaration that shows this with the handover records.