Corrugated gas pipework: fittings, protection and repairs

Note 6 of 44 · free to read

Choose compatible fittings, plan containment and access, and distinguish cover repairs from damaged gas-carrying tubing.

Corrugated stainless steel tubing (CSST) is shaped during installation to form a fixed gas-pipe route. Its fittings, cover and installation method work as a system. The examples here are for TracPipe and TracPipeCC; use the instructions for the actual product, and only do work you are competent for.

Flexible during installation, fixed in service

Being easy to bend does not make this tubing a flexible appliance hose. TracPipe is not made for repeated movement or vibration, so a cooker that is pulled out for cleaning needs a proper flexible appliance connection. A longer or larger corrugated pipe does not change that.

Use fittings the tubing maker supplies or specifies. Matching threads and size labels are not enough, and one good leak test does not make a combination approved. Use the specified transition fitting to connect to copper or steel.

At a meter that is securely restrained, the instructions permit direct connection. Where the meter is not securely restrained, first provide at least 600 mm of securely fixed rigid outlet pipework, then change to TracPipe or TracPipeCC. The connection must not put strain on the meter or its joints.

Know which surface makes the seal

An AutoFlare fitting forms its own metal sealing seat as it is tightened correctly, so keep jointing compound off its internal sealing parts. Sealing a threaded transition elsewhere in the assembly is a separate matter.

Cut the tube with the right cutter, in the valley between two corrugations. Too much cutter pressure can flatten the metal. Follow the full assembly instructions, including the end preparation and tightening: this note is not the full fitting procedure.

For comparison, a compression fitting on copper seals where the olive presses against the pipe and the fitting body; the nut's thread provides the force. PTFE tape wrapped round the olive gets in the way of that seal.

Plan the route before concealment

Check the whole proposed route for cables, junction boxes and other services before pulling tubing through a suspended floor. Take care with nails and screws when replacing the floorboards, and mark the pipe position where possible.

Keep the tubing out of structural floor slabs and structural toppings. Suitable non-structural screeds, ducts and voids have their own installation conditions, and getting to the pipe in future must not mean weakening the building. Keep fire separation and the building's other required protections.

Continuous tubing and mechanical fittings have different concealment rules. The instructions allow some buried tubing arrangements, but AutoFlare fittings must stay accessible, with an inspection space you can actually use. Extra wrapping, sand around a fitting or a note of where it is buried does not make a hidden joint acceptable.

Before screed or plaster hides the run, inspect the complete cover both visually and by touch. Find and repair damage along its length, including surfaces that are difficult to see. Looking at the ends, or testing gas tightness, will not tell you the protective cover is intact.

Containment and wall crossings

TracPipeCC has a second outer cover with channels that lead any escape towards safe, ventilated locations at the ends. Keep that route working and finish its ends as specified. It does not regulate the gas pressure, and it is not a route for boiler condensate or combustion air.

The secondary cover does not replace a suitable sleeve through a wall or floor. Follow the penetration detail as well as the requirements for the run through the void. A wall sleeve protects the crossing; secondary containment deals with an escape along the enclosed route.

Keep corrosion protection effective

Finish soldering the adjoining copper and clean off the flux before connecting it to the stainless tubing. Keep flux and solder off the corrugated pipe, inside and out. Covering the residue does not remove it.

For cover repairs and exposed steel at the fitting, use the specified TracPipe self-amalgamating silicone tape. Ordinary electrical or grease-impregnated tapes can contain chlorides that attack stainless steel. Apply the extra protection after a satisfactory tightness test, wrapping it as instructed.

Keep TracPipe and AutoFlare fittings outside an all-fuel fireplace opening. Soot and debris there can cause corrosion. Make the final connection into the firebox using suitable protected pipework.

Decide whether the cover or the metal is damaged

  • Cover damage with sound tubing: restore the protective cover using the specified tape.
  • A puncture, or a permanent crease or kink after excessive bending: replace the damaged tubing using a permitted arrangement. Tape cannot repair the metal wall that carries the gas, and a good tightness result does not change that: replace it.
  • A short, readily removable run: replace the whole length rather than splicing, which adds more joints. Complete the required examination and testing after the work.

Judge other dents or crushing against the product’s damage criteria. Not every mark is a puncture, and not every dent can be safely straightened.

Size the actual pipe

Use the manufacturer’s flow data for the corrugated section, with the correct fuel and pressure conditions. The same nominal size in copper, another CSST brand and this product does not mean the same capacity. Check which bends and end fittings the table already allows for before adding more. Check each complete meter-to-appliance route at its design demand.