Central Heating (L3)

Fabric Heat Loss and U-values

Note 5 of 17 · free to read

Calculating heat lost through the building fabric using U-values and the Q = U x A x deltaT method.

What fabric loss is

Fabric heat loss is the heat conducted out through the building envelope — external walls, windows, doors, roof and ground floor. Each element has a U-value in W/m2K: the rate of heat flow through one square metre for each degree of temperature difference. A lower U-value means better insulation.

The method

For each element:

Q = U x A x deltaT

where Q is heat loss in watts, U is the U-value (W/m2K), A is the area (m2) and deltaT is the appropriate temperature difference across the element (K). For a wall exposed to outdoor air, use the room and outdoor design temperatures. Calculate every element, then add them to get the room fabric loss.

Worked example

A living-room external wall is 6 m long and 2.4 m high, giving 14.4 m2. Subtract a 2.0 m2 window, leaving 12.4 m2 of wall.

  • Wall U-value 0.30 W/m2K, deltaT = 21 - (-3) = 24 K. Q = 0.30 x 12.4 x 24 = 89 W.
  • Window U-value 1.6 W/m2K, area 2.0 m2. Q = 1.6 x 2.0 x 24 = 77 W.

These two elements alone lose about 166 W. Repeat for roof, floor and any other exposed surfaces, using U-values supported by the actual construction details or the applicable assessment method, then carry the total forward to the room heat loss.

Heat pump heat-loss method for solid and suspended floors

Heat pump design under the MCS heat-loss method (MIS 3005-D) gives a choice of external design temperature: a less extreme figure exceeded for 99% of the hours in the year, or a colder figure exceeded for 99.6% of them. Choosing the colder 99.6% figure removes the need for a separate intermittent-heating uplift on top of the calculation, because the extra margin is already built into the lower design temperature.

The standard also treats floors in contact with the ground differently from suspended floors. A solid ground floor sits over ground that holds a large thermal mass close to the year-round average air temperature rather than the winter design temperature, so its heat-loss calculation uses the internal design temperature minus the local annual average external temperature. A suspended floor, with air beneath it rather than the ground's thermal mass, uses the ordinary external design temperature instead — using the annual average there would understate the loss.