Working out the heat needed to warm incoming fresh air using the 0.33 x N x V x deltaT method.
Why ventilation loses heat
Rooms lose heat not only through the fabric but also as cold outside air replaces warm inside air — by designed ventilation and by infiltration through gaps. That incoming air has to be heated from outside to inside temperature, and the demand adds to the room heat loss.
The method
Ventilation heat loss is estimated as:
Q = 0.33 x N x V x deltaT
- 0.33 is an approximate volumetric heat capacity of air in Wh/m3K for this calculation.
- N is the number of air changes per hour for the room.
- V is the room volume in m3.
- deltaT is the inside-to-outside temperature difference in K.
Choose the air-change input using the applicable design method, room use, airtightness and ventilation arrangement. A room’s label does not tell you its actual airflow. Where heat recovery tempers incoming air, account for it as the method requires: not all ventilation air arrives as unheated outside air.
Worked example
A living room is 5 m x 4 m x 2.4 m = 48 m3, with 1.0 air change per hour and deltaT = 24 K.
Q = 0.33 x 1.0 x 48 x 24 = 380 W.
Add this to the fabric loss for the same room to get the total room heat loss. Reducing uncontrolled draughts can reduce this load, but required ventilation must remain. Do not seal a room simply to reduce its calculated air-change loss.