Periodic maintenance tasks and diagnosing the common faults that show up at commissioning.
Periodic maintenance
Heating systems need routine care to stay efficient and safe. Typical tasks, to the manufacturer schedule, include:
- An annual appliance service (any gas work must be carried out by a Gas Safe registered engineer; this revision aid does not replace that qualification).
- Checking and topping up the corrosion inhibitor concentration with a test.
- Cleaning the magnetic filter.
- Checking system pressure, the expansion vessel charge and the pressure relief valve.
- Inspecting the flue and confirming the controls still operate.
- Water treatment does not stop at commissioning: check inhibitor concentration and general water cleanliness every year, for example at the service. At five years, re-dose or obtain the more comprehensive laboratory water analysis described by the treatment guidance, then take any required corrective action. A routine on-site concentration test is not the same as that laboratory assessment.
Fault diagnosis at commissioning
Common faults and where to look:
- No heat to a radiator: check its valves, trapped gas, flow and possible blockage. A cold whole zone also directs attention to the shared demand, pump and zone-valve path. The pattern of affected emitters helps choose the next check.
- Kettling or banging: investigate deposits, pressure, circulation and appliance controls using the fault guide. Clean only where the diagnosis and approved procedure call for it, because noise can have causes other than sludge.
- Pressure loss on a sealed system: first verify a real fall under comparable cold conditions. Check for leakage and relief discharge, including expansion-vessel problems that cause excessive pressure rise when hot. Test the vessel by its instructions: loss of charge may be repairable, while a failed diaphragm may require replacement.
- Rooms not reaching temperature: poor balancing, undersized emitters, or low flow temperature.
- Boiler short-cycling: compare minimum firing output with the active load and check flow, temperatures, controls and interlock. The minimum output matters here, not the maximum rating.
Method
Work logically from the symptom: confirm power and demand, then flow, then the appliance, against the manufacturer fault-finding guide rather than swapping parts at random.