Selecting radiators from catalogue outputs and correcting them for systems that run cooler than the test condition.
Catalogue ratings
Radiators are tested and listed to a European standard at a fixed condition, usually a deltaT of 50K — the difference between the mean water temperature and the room temperature (for example flow 75°C, return 65°C, room 20°C). The quoted output only applies at that condition.
Why correction is needed
If your system runs cooler — common on condensing and low-temperature designs — the mean water temperature is lower, the deltaT is smaller, and the radiator gives less than its catalogue figure. Use the manufacturer’s correction factor or output table to estimate output at the design conditions, or to find the required catalogue rating. Installation clearances, covers and the actual water flow can also affect delivered output.
Typical correction factors (refer to manufacturer data) are roughly:
- deltaT 50K: factor 1.00
- deltaT 40K: factor about 0.75
- deltaT 30K: factor about 0.52
Worked example
A room needs 1.5 kW. The system is designed to run at deltaT 40K.
Required catalogue output = room load / correction factor = 1.5 / 0.75 = 2.0 kW at deltaT 50K.
Using this exercise’s 0.75 factor, select a radiator rated at least 2.0 kW at deltaT50 to meet the 1.5 kW room duty. At the lower running temperature it delivers about three-quarters of that rating. Use the actual product’s factor for a real selection. Skipping this step is a frequent cause of rooms that never reach temperature on low-temperature systems.